Precautions for operation of diesel generator set

2021-11-26 打印
qq
1. The installation site shall be well ventilated. There shall be sufficient air inlet at the generator end and good air outlet at the diesel engine end. The air outlet area shall be more than 1.5 times larger than the water tank area.

2. The surroundings of the installation site shall be kept clean and articles that can produce acidic, alkaline and other corrosive gases and vapors shall not be placed nearby. If possible, fire extinguishing devices shall be equipped.

3. For indoor use, the smoke exhaust pipe must be connected to the outside, the pipe diameter must be ≥ the diameter of the smoke outlet pipe of the silencer, and the elbows of the connected pipeline should not exceed 3 to ensure smooth smoke exhaust, and the pipe should be inclined downward by 5-10 degrees to avoid rainwater injection; If the exhaust pipe is installed vertically upward, a rain cover must be installed.

4. When the foundation adopts concrete, the levelness must be measured with a level ruler during installation to fix the unit on a horizontal foundation. Special shockproof pads or foot bolts shall be provided between the unit and the foundation.

5. The unit shell must have reliable protective grounding. For generators that need neutral point direct grounding, professionals must conduct neutral grounding and configure lightning protection devices. It is strictly prohibited to use the grounding device of municipal power for neutral point direct grounding.

6. The two-way switch between the generator and the mains must be separated.